AFS / AFR / A61F-G FLOATLESS RELAY
Model: AFS / AFR / A61F-GP-N/ A61F-G / A61F-G1 / A61F-G2
Type Selection :
Sensing mode
|
Type
|
General
|
AFS-1
|
AFR-1
|
AFR-G
|
A61F-GP-N
|
A61F-G
|
A61F-G1
|
A61F-G2
|
High sensing
|
AFS-1Y
|
AFR-1Y
|
-
|
-
|
A61F-GY
|
A61F-G1Y
|
A61F-G2Y
|
Long distance
|
AFS-1L
|
AFR-1L
|
-
|
-
|
A61F-GL
|
A61F-G1L
|
A61F-G2L
|
Low density
|
AFS-1D
|
AFR-1D
|
-
|
-
|
A61F-GD
|
A61F-G1D
|
A61F-G2D
|
Two lines
|
AFS-GR
|
-
|
-
|
-
|
-
|
-
|
-
|
Number of pins
|
8P
|
8P
|
8P
|
11P
|
9P
|
13P
|
13P
|
รายละเอียด
Type
|
AFS / AFR / A61F-GP-N
|
A61F-G / A61F-G1 / A61F-G2
|
Operating voltage
|
AC(V): 110, 220, 240
|
AC(V): 110/220, 110/240, 220/380, 240/380
|
Allowable operating voltage range
|
85~110% of rated operating voltage
|
Rated frequency
|
50 / 60 Hz
|
Contact rating
|
250VAC 5A (resistive load)
|
Second voltage
|
8VAC (except High sensing 24VAC )
|
Operate resistance
|
0 ~ 4KӨ
|
Release resistance
|
15K ~ ЌӨ
|
Length of cable
|
MAX 1Km
|
Power consumption
|
AFS, AFR, A61F-GP-N and A61F-G Approx. 3.2VA , A61F-G1 Approx. 6VA
|
Life
|
Mechanical: 5,000,000 times, Electrical:100,000 times
|
Ambient temperature
|
-10 ~ +50к
|
Ambient humidity
|
MAX 85%RH
|
Weight
|
AFS-1, A61F-GP-N Approx. 160g AFS-GR Approx. 150g, AFR Approx. 200g |
A61F-G Approx. 330g A61F-G1, A61F-G2 Approx. 580g |
คุณลักษณะ
- Suitable for any electrolytic fluid surface (NO VOLATILE FLUID)
- AC operating voltage
- Protection against interference from power surge
- Low electrodes AC voltage to prevent electrolysis for longer life expectance
- 2 LED status indicator for water supply or drainage
- Automatic water supply or drainage operation and alarm for anomaly water supply*
Note: "*" indicates applicable to A61F-G2 series only
|